FEED-BACK LPG VAPORIZER USER GUIDE

1. Open the valve located under the tank. This valve allows the liquid LPG to flow through the pipe line to the feed-back vaporizer. This valve should stay open all the time to avoid the failure light alerting the user when the power is turned on. Ưn this case, the failure light can be turned off by pressing the reset button.

2. The ball valve, located on the pipe line from the top of the vaporizer to the tank, should stay open.

3. The liquid level of the tank should controlled. The order to the gas company should given before the liquid level reaches 20%. The tank should not filled over the 80% liquid level. Over filling can cause serious damage to the customers system.

4. All pipelines should be periodically controlled to prevent gas leaking.

5. The yellow light on the electric box means that the energy is on and should stay lighted when the energy is given. There are two thermostats on the system, one is for working, the other for security.

6. The energy is activated by pressing the on-off button. In this case the contactor in the electric box will activated, the heaters in the vaporizer will begin to heat and the green light will flash on the electric box.

7. The green light is connected to the working thermostat in the vaporizer and will flash until the temperature reaches the preset value (determined and set by user). The green light will turn on and off automatically while the system is on. The flashing light indicates the heaters in the vaporizer are working. When the green light is off it means that the vaporizer is heated to the preset temperature.